How to detect a common alarm through SNMP on the FM series AC units?

How to detect a common alarm through SNMP on the FM series AC units?

Published date: 17 July 2020

                                                                                                                                                          
Issue:
How can we detect a common alarm through SNMP on the FM series AC units?
 
Product line:
Network Air FM unit.
 
Environment:   
All serial Numbers.

Cause:   
 Alarm monitoring through SNMP.
  
 
Resolution:     

There is no common alarm in the FM unit however the FM does store its alarms in a table. This table has a data field that lists the number of alarms with value being equal to zero when there no alarms. By monitoring this value we can track whether there is a common alarm or not.

.iso.org.dod.internet.private.enterprises.apc.products.hardware.airConditioners.airFM.airFMAlarms.airFMAlarmConditionsTableSize
.1.3.6.1.4.1.318.1.1.13.1.6.3

 
 
As you can see, using GetIf or another mib browser, we can poll this value for the table size. We can see the value is 2 and we should have two alarms on the unit. Logging into the unit in question we confirm there are two alarms.

 
 
 
The exact alarms can also be polled from the table if the customer wants greater detail:

 
REQUIRED:
AOS 3.57
NAIRFM 3.55
NOME 6.24
POWERNETMIB 414
 
Failure to have all of these at this version or higher may result in a loss of data.
    • Related Articles

    • Smart-UPS C Series FAQ

      Published date: 14 August 2020 Issue: Smart-UPS C Series FAQ Product Line: Smart-UPS Environment: All SMC models, All Serial Numbers Cause: Product Information Resolution: What is the new Smart-UPS C series? The Smart-UPS  C series is our new entry ...
    • Common Rack Automatic Transfer Switch Scenarios and Questions

      Published date: 29 May 2019 Issue This article discusses common Rack Automatic Transfer Switch (ATS) Scenarios and Questions and provides configuration recommendations.     Product Line Rack Automatic Transfer Switches including the following models ...
    • NetBotz 300-500 Series | Password reset procedure

      Published date: 14 July 2020 Issue: How do I reset the password on a 300-500 series NetBotz appliance. Product Line: NetBotz v3 Wall Appliance: 355/356 (NBWL0355/6) & 455/456 (NBWL0455/6) NetBotz v3 Rack Appliance: 450/451 (NBRK0450/1), 550 ...
    • Smart-UPS Stacking Height Limitations

      Published date: 22 August 2018 This document describes the acceptable stacking configurations of Smart-UPS products.  To achieve the minimum possible footprint, these products can be stacked following the guidelines below. It is important to consider ...
    • Different Types of UPS Systems

      Published date: 21 May 2018 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is defined, practical applications of each are discussed, and ...