NetBotz 300-500 Series | Password reset procedure

NetBotz 300-500 Series | Password reset procedure

Published date: 14 July 2020

Issue:
How do I reset the password on a 300-500 series NetBotz appliance.

Product Line:
NetBotz v3 Wall Appliance: 355/356 (NBWL0355/6) & 455/456 (NBWL0455/6)
NetBotz v3 Rack Appliance: 450/451 (NBRK0450/1), 550 (NBRK0550), & 570 (NBRK0570)

Environment:
NetBotz 300-500 Series (all versions)

Cause:
Recover from lost client/web password or root password.

Resolution:

Recovering a Lost Web/Advanced View/Root Password
                                  

1) Locate the reset switch on the appliance.  On a wall mount version (355/455) the reset button is on the bottom next to the USB-B port.  On a Rack Mount appliance (450/550/570) the reset button is next to the Input Power connection.

2) Using a thin wire such as a paperclip, press and hold down the reset switch for ten seconds. This
will cause the system to reboot.

3. Once the system reboots, you have two minutes to log in using the following default login values:
     a. For Advanced View
          • User ID: apc
          • Password: apc
     b. For the console
          • User ID: root
          • Password: apc

4. Once you have logged in to Advanced View, change the root password and apc account password to ensure security.
Note: If you do not log in within two minutes after holding down the reset switch, you must repeat the procedure.

Note: On older Version 2 NetBotz 320, 420, and 500 appliances, the password alone can not be reset. The entire device must be reset using the "configreset" option as detailed in k-base FA158175.


    • Related Articles

    • NetBotz 250 | Reset Configuration to Defaults

      Published date: 09 July 2020 Issue: Process for resetting the configuration back to factory defaults on a NetBotz 250. Product Line: NetBotz 250 (NB250) Environment: NetBotz 250 (all versions) Resolution: 1) Log into the NetBotz 250 web interface. 2) ...
    • How to Brain Dead a Back-UPS unit. (Full UPS Logic Reset)

      Published date: 11 January 2021 Issue: To brain dead a Back-ups is to purge the charge in the brain of the UPS. Product Line: Back-UPS, Back-UPS Pro Environment: All serial numbers. Cause: Troubleshooting procedure often prescribed to clear some ...
    • Smart-UPS C Series FAQ

      Published date: 14 August 2020 Issue: Smart-UPS C Series FAQ Product Line: Smart-UPS Environment: All SMC models, All Serial Numbers Cause: Product Information Resolution: What is the new Smart-UPS C series? The Smart-UPS  C series is our new entry ...
    • How to detect a common alarm through SNMP on the FM series AC units?

      Published date: 17 July 2020                                                                                                                                                            Issue: How can we detect a common alarm through SNMP on the FM ...
    • Why are the battery charge LEDs flashing on a Smart-UPS?

      Published date: 21 July 2020 Issue: Battery Charge LED Bar Graph is flashing in unison.   Product line: Smart-UPS, Smart-UPS Online Environment: All Smart-UPS models with model numbers that begin with SU, SUA, SUM, SURT All serial numbers Cause: When ...